JS60-05L EC Sensor (Liquid-Cooled)


Features

 ● Advanced anti-polarization & signal isolation, strong anti-interference

 ● Full stainless steel, 316L electrodes with PEEK lining

 ● Wide temp range 0-50℃/0-100℃, low drift, compact & fast response

 ● Easy installation, remote readout, setup and calibration

 ● Stable performance, long service lifespan 

 

    • Commodity name: JS60-05L EC Sensor (Liquid-Cooled)

    Overview

    The JS60-05L EC Sensor is tailored for liquid cooling applications. Impurities build up in coolant during prolonged system operation and boost conductivity, easily leading to server short circuits and device malfunctions.Featuring advanced anti-polarization and built-in signal isolation, it boasts strong anti-interference capability. Built in full stainless steel with 316L inner & outer electrodes and PEEK lining, it is simple to install. Compatible with propylene glycol, ethylene glycol, deionized water and more, it ensures precise, steady and durable conductivity monitoring to guarantee liquid cooling system safety.

     

    Applications

    ● Liquid cooling field

    ● Eco-environmental monitoring

    ● Hydrology & water resources

    ● Smart fish farming / Aquatic breeding

     

    Technical Parameter

    Item

    Technical Specification

    Measurement principle

    Variable frequency AC method

    Range

    0~5000us/cm

    Accuracy

    1%FS

    Resolution

    1μS/cm

    Supply

    7-28 VDC,Power consumption:<0.2W

    Output

    RS485 and 4-20mA at the same time

    Pressure resistance

    0.6MPa

    Screw thread

    Upper:G3/4

    Main material

    316 L

    Applicable medium

    Deionized water, PG25 ,EG25

    O-ring material

    EPDM

    Operating temperature

    0-+50℃(High temperature customizable)

    Response time

    1s

    Drift

    ≤0.3%FS/24h

    Temperature compensation

    Automatic (Temperature 0-100℃)

    Ingress protection

    IP68

    Storage

    -20-80℃@20%-90%RH

    Cable length

    5m default , other cable lengths can be customized

     

    Dimensions & Mounting

    Unit:mm

    EC L_副本

     

    Electrode Maintenance and Installation

    Note: Clean the conductivity electrode regularly using warm water with a mild detergent. For stubborn deposits, use a 20 g/L diluted hydrochloric acid solution, then rinse thoroughly with deionized water.

    EC Installaration-1

    Note: Regardless of the installation method, please avoid air bubbles in the conductivity cell.

PRODUCT APPLICATION

undefined

undefined

CUSTOMER TESTIMONIALS

undefined

undefined

CERTIFICATE

CE Certificate

CE Certificate

CE Certificate

CE Certificate

CE Certificate

CE Certificate

Why Choose Joysense?

图片名称

Comprehensive Product Range

Our diverse portfolio of sensors allows us to offer customized monitoring solutions for a wide array of sectors, addressing specific environmental and operational needs.

图片名称

Customized Solutions

Each product is developed through rigorous research and development, coupled with strict quality control measures, ensuring reliable performance across various environments—from urban infrastructure to remote field applications. 

图片名称

Customized & Reliable Solutions

We offer tailored solutions designed to meet the unique needs of your projects, supported by our robust manufacturing capabilities and extensive testing processes. 

图片名称

Global Trust & Service

Our products are trusted by clients worldwide, and we provide comprehensive customer support, including technical assistance, on-time delivery, and responsive after-sales service. 

LET'S TALK ABOUT YOUR PROJECT

Tell us your requirements and our team will provide the right custom solution soon.

%{tishi_zhanwei}%